parameters cannot be changed whether the frequency converter is in whatever state; when changing the
function code parameter, the parameter’s range, unit and related explanations should also be paid attention.
Function code group
number
Communication accessing
address
Communication modified function address
in the RAM
Group F0~FE
0xF000
~
0xFEFF
0x0000
~
0x0EFF
Group A0~AC
0xA000
~
0xACFF
0x4000
~
0x4CFF
Group U0
0x7000
~
0x70FF
Note: since EEPROM is frequently restored, so the service life of EEPROM shall be reduced, therefore,
some function codes have no need to be stored under the communication mode, if only the value in the
RAM modified.
If it is the Group F parameter, whether only the high position F for the function code address changes to 0,
then the function can be achieved.
If it is the Group A parameter, whether only the high position A for the function code address changes to 4,
then the function can be achieved.
The corresponding function code address is shown as below:
High byte: 00~0F(Group F)
、
40~4F(Group A)
Low byte: 00~FF
For example:
If function code F3-12 is not stored in EEPROM, then the address is shown as 030C;
If function code A0-05 is not stored in EEPROM, then the address is shown as 4005;
The address presentation can only act the writing RAM, without acting the reading action. When reading, it
is the invalid address.
As for all the parameters, command code 07H can also be used for realizing the function.
Stop /operating parameter part:
Parameter
address
Parameter description
Parameter
address
Parameter description
1000H
* Communication set value
(decimal)
–10000 ~10000
1010H
PID set-up
1001H
Operation frequency
1011H
PID feedback
1002H
Bus voltage
1012H
PLC steps
1003H
Output voltage
1013H
-
1004H
Output current
1014H
Feedback speed, the unit is 0.1Hz
Parameter
Parameter description
Parameter
Parameter description