The User Manual of JAC200 Series General Frequency Converter
- 37 -
Function
code
Name
Set range
Default
value
Chan
ge
deceleration time 2
F8-27
Terminal jog
precedence
0: Invalid 1: Valid
0
☆
F8-28
Frequency detection
value (FDT2)
0.00Hz
~
Maximum frequency
50.00Hz
☆
F8-29
The lagged value of
frequency detection
(FDT1)
0.0%
~
100.0% (FDT2 electrical level)
5.0%
☆
F8-30
Detection value 1
of arbitrary arriving
frequency
0.00Hz
~
Maximum frequency
50.00Hz
☆
F8-31
The detected width 1
of arbitrary arriving
frequency
0.0%
~
100.0% (Maximum frequency)
0.0%
☆
F8-32
The detection value 2
of arbitrary arriving
frequency
0.00Hz
~
Maximum frequency
50.00Hz
☆
F8-33
The detected width 2
of arbitrary arriving
frequency
0.0%
~
100.0% (Maximum frequency)
0.0%
☆
F8-34
The detection level
of zero current
0.0%
~
300.0%
Be 100.0% corresponding to the rated
current of motor
5.0%
☆
F8-35
The delayed time of
current detection
0.01s
~
600.00s
0.10s
☆
F8-36
Output current
over-limit
0.0% (Not detected)
0.1%
~
300.0% (The rated current of
motor )
200.0%
☆
F8-37
The delayed time of
output current
over-limit detection
0.00s
~
600.00s
0.00s
☆
F8-38
Arbitrary arriving
current 1
0.0%
~
300.0% (The rated current of
motor )
100.0%
☆
F8-39
The width of
arbitrary arriving
current 1
0.0%
~
300.0% (The rated current of
motor )
0.0%
☆
F8-40
Arbitrary arriving
current 2
0.0%
~
300.0% (The rated current of
motor )
100.0%
☆
F8-41
The width arbitrary
0.0%
~
300.0% (
The rated current of
0.0%
☆