The User Manual of JAC200 Series General Frequency Converter
- 102 -
Fig. 6-11 Diagram for S-curve acceleration/deceleration A
Fig. 6-12 Diagram for S-curve Acceleration/Deceleration B
F6-10
Stop mode
Default value
0
Set range
0
Deceleration stop
1
Free stop
0: Deceleration stop
After the stop command is enabled, the frequency converter shall reduce output frequency according to
deceleration time and the machine shall be stopped after the frequency is reduced to
0.
1: Free stop
After the stop command is valid, the frequency converter shall terminate the output. Now the motor shall
stop freely based on mechanical inertia.
F6-11
Initial frequency of stop DC
braking
Default value
0.00Hz
Set range
0.00Hz
~
Maximum frequency
F6-12
Waiting time of stop DC braking
Default value
0.0s
Set range
0.0s
~
100.0s
F6-13
Stop DC braking current
Default value
0%
Set range
0%
~
100%
F6-14
Stop DC braking time
Default value
0.0s