The User Manual of JAC200 Series General Frequency Converter
- 68 -
1
0.1 second
2
0.01 second
JAC200 provides 3 kinds of the unit of acceleration/deceleration time for meeting the requirement of all
kinds of site, and they are 1 second, 0.1 second and 0.01 second.
Note:
When modify the function parameter, the decimal places which are displayed by 4 groups of
acceleration/deceleration time will be changed, and the corresponding acceleration/deceleration time will be
changed too. You shall watch particularly during using it.
F0-21
Offset frequency of auxiliary
frequency source when
superposition
Default value
0.00Hz
Set range
0.00Hz-maximum frequency F0-10
This function code is valid when the frequency source is main/auxiliary operation.
When make frequency source as main and auxiliary operation, can set offset frequency as F0-21.
Superimpositions of offset frequency and the result of main and auxiliary operation are taken as the ultimate
frequency setting value. Make the frequency setting is more flexible.
F0-22
Frequency instruction
resolution
Default value
2
2
0.01Hz
This parameter is used to confirm the all resolution about frequency.
F0-23
Stop memory selection of figure set
frequency
Default value
0
Set range
0
No memory
1
Memory
This function is valid only when the frequency source is figure setting.
The “no memory” means figure set frequency value is restored to F0-08(preset frequency) after frequency
converter stopping. The frequency modification of key ▲, ▼ or the terminal UP, DOWN will be reset.
The “memory” means figure set frequency value is kept to the set frequency of the last stopping after
frequency converter stopping. The frequency modification of key ▲, ▼ or the terminal UP, DOWN will be
valid.
F0-24
The selection of motor
Default value
0