User Manual
828
Rev. 1.1
2019-03-18
TLE984xQX
Microcontroller with LIN and Power Switches for Automotive Applications
10-Bit Analog Digital Converter (ADC1)
ADC1 or Filter Output Channel 10
ADC1_FILT_OUT10
Offset
Reset Value
ADC1 or Filter Output Channel 10
98
H
see
Field
Bits
Type
Description
RES
31:19
r
Reserved
Always read as 0
OF10
18
r
Overrun Flag
Indicates if the result register is overwritten with new
content (bit is set if VFx = 1 and new result is updated by
hardware.
Note:
Only set in WFRx = DISABLE and no software
mode, clear on read of FILT_OUT_CH10 register
0
B
NO OVERRUN
, Result register not overwritten
1
B
OVERRUN
, Result register overwritten
VF10
17
rh
Valid Flag
Indicates valid contents in result register bit field
ADC1_OUT_CH10
Note:
Bit is set by hardware on update of result
register and it is cleared by software once the
FILT_OUT_CH10 register is read. The hardware
update has priority than the software read in
case the event occurs at the same cycle.
0
B
NOT VALID
, No new valid data available
1
B
VALID
, Result register contains valid data and has
not yet been read
WFR10
16
rw
Wait for Read Mode
Enables wait for read mode for result register
0
B
DISABLE
, overwrite mode
1
B
ENABLE
, wait for read mode enabled
RES
15:12
r
Reserved
Always read as 0
31
19
r
RES
18
18
r
OF10
17
17
rh
VF10
16
16
rw
WFR1
0
15
12
r
RES
11
0
r
FILT_OUT_CH10