Table 79 Barometric Sensor Output – CONTINUED
Atmospheric Pressure inHg (mb)
Output Voltage VDC
29.0 (982.1)
2.30
29.2 (988.8)
2.32
29.4 (995.6)
2.33
29.6 (1002.4)
2.35
29.8 (1009.1)
2.37
30.0 (1015.9)
2.39
30.2 (1022.7)
2.40
30.4 (1029.5)
2.42
30.6 (1036.2)
2.44
30.8 (1043.0)
2.46
31.0 (1049.8)
2.47
4.16.2.2
Flowmeter Troubleshooting
If having issues with a flowmeter go to the calibration tab and select flowmeter calibration (see
Figure 133. Calibrate Valve Flow Screen
Flowrate Is Erroneous
A.
Remove flowmeter paddlewheel and verify paddlewheel is clean and spins freely.
B.
Recalibrate flowmeter see section 5.3 (page 178).
No Flowrate Is Displayed
A.
Observe Flow column readings:
If there is an issue with connection to flowmeter, Flow column reading will be 6553.
If there is no issue with flowmeter connection, Flow column reading will be 0.
(When there is no flow on the system.)
If Flow column reading is reading 6553 and associated valve has a flowmeter, verify
harness connections.
B.
If SAM displays a COMM loss for associated valve (in Auto Mode) , check power
and/or CAN connections to valve. See paragraph 4.3.5 (page 48) and sec-
Summary of Contents for Hale Sam
Page 2: ......
Page 37: ...17 Figure 14 SAM Blue CAN Buss Architecture With Three SAM Control Centers Diagram...
Page 38: ...18 Figure 15 SAM Green CAN Buss Architecture With Three SAM Control Centers Diagram...
Page 39: ...19 Figure 16 SAM Red CAN Buss Architecture With Three SAM Control Centers Diagram...
Page 40: ...20 Figure 17 SAM System Drain And Pneumatic Diagram...
Page 41: ...21 Figure 18 SAM Speaks Diagram...
Page 42: ......
Page 58: ...38 THIS PAGE INTENTIONALLY BLANK...
Page 62: ...42 THIS PAGE INTENTIONALLY BLANK...
Page 192: ...172 THIS PAGE INTENTIONALLY BLANK...
Page 206: ...186 THIS PAGE INTENTIONALLY BLANK...
Page 220: ...200 THIS PAGE INTENTIONALLY BLANK...