48
4.3.4.2
Export Datalogger From SAM Pump Controller
When directed by Hale Customer Service, download the data log file from the SAM Pump Control-
ler by performing the following.
A.
Open pump operator panel.
B.
Gain access to USB dongle on rear of SAM Pump Controller.
C.
Connect a USB 2.0 flash drive to USB dongle. (See Figure 24, page 33; do NOT
connect the Hale USB Key for this purpose.)
D.
Temporally, close panel.
E.
On SAM Control Center, touch MANUAL MODE button. See Figure 1 (page 11).
F.
Touch YES button. (See Figure 2, page 11.)
G.
On SAM Pump Controller, touch and hold system options button until loading icon
completes circle (see Figure 25, page 34) and Menu screen is displayed (see Fig-
H.
Touch Export Datalogger text.
I.
Wait while Saving file to USB stick … is displayed.
J.
When
Data log file has been saved to the USB stick.
displays, on rear of SAM
Pump Controller, remove USB flash drive.
NOTE
Reference FSG-MNL-00210 (SAM OIM), section 4 (System Overview) for icon and
screen definitions/description information.
K.
On MENU screen, touch Back To Previous Screen icon.
L.
Close pump operator panel.
4.3.5
SAM Wire Harness Guidelines
SAM utilizes three SAE J1939 compliant CAN (500 kbit/s) buses: the Blue (loom color indicates
the associated bus) bus interfaces the apparatus (primarily the ECU) and SAM; the Green bus
provides controls and indications for the intake and sensors portion of the SAM system; and the
Red bus provides controls and indications for the discharge portion of the SAM system. It is im-
portant to adhere to the following guidelines.
•
Do NOT add or remove any device from SAM without first contacting Hale
•
Always adhere to J1939 standards for physical length and connection
•
Provide a service loop and strain relief for all harness connectors
(water leakage can lead to service issues)
•
Each of the three buses must be properly terminated to operate properly
•
All SAM circuit breakers are auto resetting
•
Most SAM bus connectors require standard Deutsch procedures and parts
Optionally, SAM may include a fourth CAN bus to support an added FOAM or CAFS system (the
Orange bus). Contact Hale for all bus bridge issues or reference the following Hale manuals for
other types of FOAM or CAFS issues.
•
SmartFOAM Electronic Foam Proportioning Systems Models: Class A only–1.7AHP, 2.1A
Class A/B–3.3, 5.0, 6.5 Description, Installation, and Operation Manual (FSG-MNL-00158)
Summary of Contents for Hale Sam
Page 2: ......
Page 37: ...17 Figure 14 SAM Blue CAN Buss Architecture With Three SAM Control Centers Diagram...
Page 38: ...18 Figure 15 SAM Green CAN Buss Architecture With Three SAM Control Centers Diagram...
Page 39: ...19 Figure 16 SAM Red CAN Buss Architecture With Three SAM Control Centers Diagram...
Page 40: ...20 Figure 17 SAM System Drain And Pneumatic Diagram...
Page 41: ...21 Figure 18 SAM Speaks Diagram...
Page 42: ......
Page 58: ...38 THIS PAGE INTENTIONALLY BLANK...
Page 62: ...42 THIS PAGE INTENTIONALLY BLANK...
Page 192: ...172 THIS PAGE INTENTIONALLY BLANK...
Page 206: ...186 THIS PAGE INTENTIONALLY BLANK...
Page 220: ...200 THIS PAGE INTENTIONALLY BLANK...