180
F.
Touch red dot (next to Friendly Name) to select valve for testing.
(See Figure 148.)
Figure 148. Enter Externally Determined Flow Rate
G.
Touch and hold Run Open button (see bottom of Figure 148) to fully open valve
under test.
H.
On external flow test equipment, determine actual flow of valve under test.
I.
On CALIBRATE VALVE FLOW screen (right-hand side), enter the results of the flow
test as follows.
Touch applicable units. (Match units for the flow value from previous step.)
Using key pad, sequentially touch digits of flow value.
Touch DONE button
Touch SEND FLOW button.
NOTE
If entry errors are made that cause the calibration to fail (or become unresponsive),
touch the perform Set Flow (Factory Default) procedure (see paragraph 5.3.1, page
J.
Repeat Step F thru Step I.4 until all desired/required discharge flows have ben
calibrated.
K.
Touch Home button.
L.
Cycle SAM system power.
5.3.3
Calibration With AKROVIEW Diagnostic Software
PERFORMING THIS PROCEDURE CAUSES SAM TO EXIT AUTO MODE.
If already using Akroview or Akroview II the discharge valves may be calibrated using a computer,
a USB to CAN adapter, and the software. Reference the Akron Brass 6046 Diagnostic Interface
Summary of Contents for Hale Sam
Page 2: ......
Page 37: ...17 Figure 14 SAM Blue CAN Buss Architecture With Three SAM Control Centers Diagram...
Page 38: ...18 Figure 15 SAM Green CAN Buss Architecture With Three SAM Control Centers Diagram...
Page 39: ...19 Figure 16 SAM Red CAN Buss Architecture With Three SAM Control Centers Diagram...
Page 40: ...20 Figure 17 SAM System Drain And Pneumatic Diagram...
Page 41: ...21 Figure 18 SAM Speaks Diagram...
Page 42: ......
Page 58: ...38 THIS PAGE INTENTIONALLY BLANK...
Page 62: ...42 THIS PAGE INTENTIONALLY BLANK...
Page 192: ...172 THIS PAGE INTENTIONALLY BLANK...
Page 206: ...186 THIS PAGE INTENTIONALLY BLANK...
Page 220: ...200 THIS PAGE INTENTIONALLY BLANK...