4.3 Stop position / operating conditions (AVD) setting/adjustment
4-10
4. Operation
Pressing operation setting
Setting
item
Unit
Explanation
Pressing
starting
point
degree
The position where pressing operation starts.
Enter as the distance from the home position.
Entries can be made in increments of 0.01 degrees.
Pressing
force
%
or
N·m
The current limit value during the pressing operation.
Set between 20 and 70%.
[Switch units] can be used to input values in N·m units.
The pressing speed is 20 deg./s.
If [V: Velocity] is set to 20 deg./s or below, pressing will
take place at the speed of [V: Velocity].
Caution
The pressing force displayed in N·m units serves as a guideline.
→ Refer to "Pressing force and current limit value relationship" on pages 1-9/20.
When the pressing speed is 20 deg./s or less, the pressing force will become unstable,
and failure to operate normally is possible.
Check [Push].
The screen will switch to
the pressing operation
window.
Action
1
Summary of Contents for ELECYLINDER EC-RTC12
Page 2: ......
Page 26: ...1 5 Accessories 1 35 Power I O cable 1 35 Power I O connector 1 36 ...
Page 64: ......
Page 78: ...2 14 2 Installation ...
Page 80: ......
Page 100: ...3 20 3 Wiring ...
Page 124: ...4 22 4 Operation ...
Page 126: ......
Page 132: ...5 6 5 Preventive Predictive Maintenance ...
Page 134: ......
Page 148: ...6 14 6 Parameters ...
Page 150: ......
Page 168: ...7 18 7 Troubleshooting ...
Page 170: ......
Page 208: ......
Page 212: ......
Page 214: ...10 2 10 Life ...
Page 216: ......
Page 219: ...Appendix 12 1 Index 12 1 12 2 Revision history 12 4 ELECYLINDER Chapter12 ...
Page 220: ......
Page 225: ......