4.4 I/O signals
4-16
4. Operation
[PE0] [PE1] signals: Pressing complete output (backward end / forward end)
● Turns ON when "pressing complete" is determined during pressing operation.
● Turns OFF if no contact can be made.
→ Refer to “
Pressing Operation
(page 4-20)” for details about pressing operation.
[*ALM] signal: Alarm output
● Turns ON when the ELECYLINDER is in normal status.
Turns OFF when an alarm occurs.
● Always monitor the *ALM signal using the master device.
If it turns OFF, immediately take appropriate safety countermeasures with the
equipment as a whole.
→ For details, refer to "7.4 Troubleshooting by alarm groups".
Signal input time constant
In order to prevent mis-operation due to chattering or noise, [ST0], [ST1] and [RES] signals are
set with a 6 ms input time constant.
For signals less than 6 ms the device will not consistently recognize the signal, so input signals
continuously for 6 ms or longer.
6 ms
Input signal
(6 ms or more)
Input signal
(Less than 6 ms)
Summary of Contents for ELECYLINDER EC-RTC12
Page 2: ......
Page 26: ...1 5 Accessories 1 35 Power I O cable 1 35 Power I O connector 1 36 ...
Page 64: ......
Page 78: ...2 14 2 Installation ...
Page 80: ......
Page 100: ...3 20 3 Wiring ...
Page 124: ...4 22 4 Operation ...
Page 126: ......
Page 132: ...5 6 5 Preventive Predictive Maintenance ...
Page 134: ......
Page 148: ...6 14 6 Parameters ...
Page 150: ......
Page 168: ...7 18 7 Troubleshooting ...
Page 170: ......
Page 208: ......
Page 212: ......
Page 214: ...10 2 10 Life ...
Page 216: ......
Page 219: ...Appendix 12 1 Index 12 1 12 2 Revision history 12 4 ELECYLINDER Chapter12 ...
Page 220: ......
Page 225: ......