5.2 Maintenance information
5-3
5. Preventive
/Predi
ctive Maintenance
Overload warning level
Name
Symbol Unit
Input range
Default setting
at shipping
Overload warning
level
OLWL
%
50 to 100
100
(disabled setting)
● With the motor temperature rise value which triggers an overload alarm as 100%, set the
level to output an overload warning between 50 and 99%.
● When the motor temperature rise value during operation exceeds the ratio set as "overload
warning level", the user will be notified with "Maintenance warning 3".
● When the motor temperature rise value falls below the ratio set as "overload warning level",
"Maintenance warning 3" will be automatically cleared.
● When "Maintenance warning 3" is output, investigate the cause of the increase in load.
Maintenance such as greasing or reviewing the operating conditions is recommended.
● Setting it to "100%" will disable this function.
Temperature change
under abnormal
conditions
Temperature change under normal conditions
Time
⇒
Warning output without stopping operation
Motor temperature
⇒
⇒
Stops operation
Overload alarm detection value
(100%)
Overload warning level set value
(50 to 99%)
Load increase
Alarm output
Warning
output
Perform
maintenance
Breakdowns and malfunctions can
be prevented by performing
maintenance after a warning is
output.
Summary of Contents for ELECYLINDER EC-RTC12
Page 2: ......
Page 26: ...1 5 Accessories 1 35 Power I O cable 1 35 Power I O connector 1 36 ...
Page 64: ......
Page 78: ...2 14 2 Installation ...
Page 80: ......
Page 100: ...3 20 3 Wiring ...
Page 124: ...4 22 4 Operation ...
Page 126: ......
Page 132: ...5 6 5 Preventive Predictive Maintenance ...
Page 134: ......
Page 148: ...6 14 6 Parameters ...
Page 150: ......
Page 168: ...7 18 7 Troubleshooting ...
Page 170: ......
Page 208: ......
Page 212: ......
Page 214: ...10 2 10 Life ...
Page 216: ......
Page 219: ...Appendix 12 1 Index 12 1 12 2 Revision history 12 4 ELECYLINDER Chapter12 ...
Page 220: ......
Page 225: ......