7.4 Troubleshooting by alarm groups
7-13
7.
Tro
ublesh
ooting
Alarm group C: Controller abnormality alarm
Controller abnormality occurred.
No.
Cause
Countermeasure
1
The controller is affected by the noise of a
peripheral device and cannot operate normally.
Shut down the power supply of the peripheral
device and operate only
with the
ELECYLINDER, then check to see whether
this alarm persists.
If it does not, there is a possibility that the
ELECYLINDER
is affected by the noise from
the peripheral device.
Reconsider the noise countermeasures
(grounding, power line wiring, electrostatic
shielding, etc.) for the peripheral device.
2
If this alarm recurs after performing the
inspection above and improving the power
supply environment, it is highly likely that the
controller has failed.
Replace the controller cover assembly.
→ For details, refer to "
Controller
replacement
(page 8-15 to 18)".
Summary of Contents for ELECYLINDER EC-RTC12
Page 2: ......
Page 26: ...1 5 Accessories 1 35 Power I O cable 1 35 Power I O connector 1 36 ...
Page 64: ......
Page 78: ...2 14 2 Installation ...
Page 80: ......
Page 100: ...3 20 3 Wiring ...
Page 124: ...4 22 4 Operation ...
Page 126: ......
Page 132: ...5 6 5 Preventive Predictive Maintenance ...
Page 134: ......
Page 148: ...6 14 6 Parameters ...
Page 150: ......
Page 168: ...7 18 7 Troubleshooting ...
Page 170: ......
Page 208: ......
Page 212: ......
Page 214: ...10 2 10 Life ...
Page 216: ......
Page 219: ...Appendix 12 1 Index 12 1 12 2 Revision history 12 4 ELECYLINDER Chapter12 ...
Page 220: ......
Page 225: ......