N700E INSTRUCTION MANUAL
3-24
A52
Automatic Voltage Regulation (AVR)
0: Constant ON
1: Constant OFF
2: OFF During Deceleration (On otherwise)
AVR enables the constant output regardless input power fluctuation.
Related Parameters:
A53
Motor Input Voltage
230V Class Setting: 200/220/230/240 LF Models
460V Class Setting: 380/400/415/440/460/480 HF Models
Select input voltage for respective N700E VFD Models
Related Parameters:
A54
Acceleration Time 2
Range: 0 .1 ~ 999.9 Sec in 0.1 Sec
Range: 1000 ~ 3000 Sec in 1.0 Sec
In addition to Acceleration Time 1 in F02, Second acceleration time can be specified. Its
value can also be entered by input terminal 2CH
Related Parameters:
A55
Deceleration Time 2
Range: 0 .1 ~ 999.9 Sec in 0.1 Sec
Range: 1000 ~ 3000 Sec in 1.0 Sec
In addition to deceleration Time 1 in F03, Second acceleration time can be specified. Its
value can also be entered by input terminal 2CH
Related Parameters:
A56
Accel/Decel 2 Command Select
0: 2CH from Input Terminal
1: Parameters (A54,A55, A57,A58)
Select the transition frequency point about acceleration/deceleration
by input terminal or frequency
Related Parameters: C01~C12, A57~A60
A57
Accel 2 Transition Frequency
Range: 0 .00 ~ Max Frequency(A04) in 0.01Hz
In addition to Acceleration Time 1 in F02, Acceleration Time 2 can be specified. Its value
can also be entered by input terminal 2CH
Related Parameters:
A58
Decel 2 Transition Frequency
Range: 0 .00 ~ Max Frequency(A04) in 0.01Hz
In addition to Deceleration Time 1 in F03, Deceleration Time 2 can be specified. Its value
can also be entered by input terminal 2CH
Related Parameters:
A57
FW(Run)
t
A58
A54
F02
F03
A55
F
A04