N700E INSTRUCTION MANUAL
3-3
Code
Name
Edit
Range
Unit Res Default
Multi-speed Frequency Setting
A11
~
A25
Multiple Speed Frequency
Setpoints
O
0.01 to A04 (Max Frequency)
Hz 0.01
A11:5Hz
A12:10Hz
A13:15Hz
A14:20Hz
A15:30Hz
A16:40Hz
A17:50Hz
A18:60Hz
A19:0 Hz
A25:0 Hz
A26 Jog Frequency
O 0.50 to 10.00
Hz 0.01
0.50
A27 Jog Stop Mode
X
0: Free Run Stop
1: Deceleration
2: DC Injection Braking
-
-
0
A28 Torque Boost Mode
X 0: Manual
1: Automatic
-
-
0
A29 Manual Torque Boost Voltage
Setpoint
O 0.0 to 50.0
%
0.1
1.0
A30 Manual Torque Boost Frequency
Setpoint
O 0.0 to 100.0
%
0.1
10.0
A31 Motor Control Method
X
0: Constant Torque
1: Variable Torque
2: Sensorless Vector Control
-
-
0
A32 Voltage Gain Factor
O 20.0 to 110.0
%
0.1
100.0
DC Injection Braking Settings at VFD Stop
A33 DC Injection Braking
X 0:Disabled
1 :Enabled
-
-
0
A34 DC Injection Braking Frequency
Setpoint
X 0.50 to 10.00
Hz 0.01
0.50
A35 DC Injection Braking Delay Time X 0.0 to 5.0
Sec 0.1
0.0
A36 DC Injection Braking Force at
Stop
O 0.0 to 100.0
%
0.1
50.0%
(≤30HP)
10.0%
(≥40HP)
7.0%
(≥250HP)
A37 DC Injection Braking Time at
Stop
X 0.0 to 10.0
Sec 0.1
0.0
DC Injection Braking Settings at VFD Start
(b42 ~ b46) – extended for better functional control
Frequency-related Functions
A38 Frequency Upper Limit
X A39 to A04 …0 : Disabled
Hz 0.01
0.00
A39 Frequency Lower Limit
X 0.00 to Frequency Upper Limit(A38)
Hz 0.01
0.00
A40
A42
A44
Skip Output Frequencies
X 0.00 to Max Frequency (A04)
Hz 0.01
0.00
A41
A43
A45
Skip Frequency Range
X 0.00 to 10.00
Hz 0.01
0.00