N700E INSTRUCTION MANUAL
3-65
Set 6: Operation by Communication (COM)
The digital outputs can be controlled by modbus communication
Parameter
Address
Description
Digital Output
(Relay Output)
0x1001
Refer to below bit table 0: Stop
Write Command has to set C13~C16 = 6
Digital Output Bit Table
1
st
byte
Bit7
Bit6
Bit5
Bit4
Bit3
Bit2
Bit1
Bit0
Reserved
2
nd
byte
Bit7
Bit6
Bit5
Bit4
Bit3
Bit2
Bit1
Bit0
Reserved
AL0~2
RN2~3
RN0~1
Set 7: System Overload Detection (SOD)
The inverter System Overload is active by b57 level
Code
Set Value
Description
C13
7
Set Intelligent Relay Out 1 Terminal to SOD
C16
0
Set C13 to Normally Open to Form A configuration
If set to 1, Form B configuration (Normally Closed)
b56
1 or 4 or 6
System Overload Detection or Detection with Fault (E23)
b57
[20~200] % System Overload Detection Level
10% hysteresis
10% hysteresis
b59
b59
b57
Motor Current
System Overload Detection
@ OD signal LOW
AL0 AL1 AL2
AL0 AL1 AL2
@ OD signal HIGH