N700E INSTRUCTION MANUAL
3-58
UP
MOTOR
RPM
FW(Run)
DOWN
When both Up & Down signals
are On at the same time,,
frequency stays still
CM1
6
P24
Down
5
4
3
2
1
Up
FW
C28
UP/DOWN Initial Value Saving
Selects if the Initial Value is going to be saved or not when power is removed.
0: Disabled
1: Enabled
C29
UP/DOWN Initial Value Setting
Range: 0.00 ~ Max Frequency(A04) in 0.01 Hz
Sets the UP/DOWN Initial Value. This value is then used as the starting frequency
reference when the next Run Command is given.
UP Command
Initial value Clear
Output frequency
UP/DOWN reference
Run Command
C30
UP/DOWN Reference Arriving Time
Range: 0.1 ~ 3000 Sec in 0.1 Sec
Sets the rate of change for the reference when this feature is applied.
UP Command
DOWN Command
Output Frequency
C30 (UP/DOWN Ref Changing Time)