N700E INSTRUCTION MANUAL
3-7
Code
Name
Edit
Range
Unit Res Default
Other Functions
b10 Start Frequency Setpoint
X 0.50 to 10.00
Hz 0.01
0.50
b11 PWM Carrier Frequency
O 1.0 to 16.0
kHz 0.1 2.0~5.0
b12 Initialization Mode
X
0: Clear Trip History
1: Parameter initialization except
-
-
0
b13 Country Code
X
0: Korea
1: Europe
2: US
-
-
2
b14 RPM Display Scale Factor
O 0.01 to 99.99
-
0.01
1.00
b15 Stop Key Function
X
0: Enabled
1: Disabled
-
-
0
b16
Resume Frequency on FRS
Cancellation
X
0: Restart from 0 Hz
1: Restart from frequency
corresponding motor speed
-
-
0
b17 Modbus Node ID
X 1 to 32
-
1
1
b18 Ground Fault Detection Setpoint X 0.0 to 100.0
%
0.1
0.0
b19 Speed Search : Current level
O 90 to 180
%
1
100
b20 Speed Search:
Voltage Increase
O 10 to 300
%
1
100
b21 Speed Search:
Voltage Decrease
O 10 to 300
%
1
100
b22 Speed Search:
Speed Decrease
O 1.0 to 200.0
(On display: 10~2000)
%
0.1
100.0
(1000)
b23 Frequency Match
O
0: Start from 0 Hz
1:Start from frequency corresponding
motor speed
-
-
0
b24 Fault Relay Select
O
0: Inactive for the Under
Voltage trip signal
1: Inactive during auto reset
2: Active every trip
3: Active for the Under
Voltage trip signal endlessly
-
-
0
b25 Stop Method
O 0: Ramp to Stop
1: Coast to Stop (Free Run Stop)
-
-
0
b26
HD/ND
(Torque Type) Select
X 0: Heavy Load (Constant Torque)
1: Normal Load (Variable Torque)
-
-
0
b27
Input Phase Loss Detection
Period
X 0 to 100
Sec
1
10
b28
Communication Time Out
Detection
O 0 to 60…0 : Disabled
Sec
1
0
b29
Communication Time Out
Detection Mode
O
0: Always Active
1: Active Only when VFD is Running
-
-
0
b30 Display at Power On
O 1 to 13 (for d01 ~ d13)
-
-
1
b31
RXP-RXN terminal
Communication Baud Rate
X
1: 2400bps
2: 4800bps
3: 9600bps
4: 19200bps
-
-
3