N700E INSTRUCTION MANUAL
3-68
Range: 0.0 ~ 250.0 % in 0.1
Program the gain factor to FM motoring setting
C20
FM Offset
Range: -3.0 ~10.0 % in 0.1
Program the offset factor to FM monitoring setting
C21
Motor Overload Alarm
Range: 10.0 ~200.0 % in 0.1
Program a level of the rated motor current
C22
FA2 SetPoint at Acceleration
Range: 0.00 ~ A04 Hz in 0.01
Program the frequency arrival threshold during acceleration
C23
FA2 SetPoint at Deceleration
Range: 0.00 ~A04 Hz in 0.01
Program the frequency arrival threshold during deceleration
C24
PID Error Tolerance
Range: 0.0 ~100.0 % in 0.1
Program the allowable PID loop error magnitude
C25
AMI Output Setting
Program what output performance to be monitored from following selections
0: Output Frequency
1: Output Current
2: Output Voltage
3: Output Power
4: Output Torque Monitor
5: Operation by Communication
Set 0: Output Frequency Monitoring
Monitor the VFD output frequency value. The highest analog output value is the
maximum frequency value. The indicator accuracy after the adjustment is about +/- 5%.
Set 1: Output Current Monitoring
Monitor the VFD output current value. The highest analog value is the 200% of rated
VFD current. The indicator accuracy after the adjustment is about +/- 10%.
Set 2: Output Voltage Monitoring
Monitor the VFD output voltage value. The highest analog value is the 100% of rated
VFD voltage out. The indicator accuracy after the adjustment is about +/- 10%.
Set 3: Output Power Monitoring
Monitor the VFD output power value. The highest analog value is the 200% of rated
VFD power out. The indicator accuracy after the adjustment is about +/- 10%
Set 4: Output Torque Monitor
Monitor the VFD output torque value. The highest analog value is the 150% of rated
VFD output torque. The indicator accuracy after the adjustment is about +/- 10%
AMI output
Torque
4mA
-150%
12mA
0%
20mA
+150%
Set 5: Operation by Communication