N700E INSTRUCTION MANUAL
3-86
N700E
*Eu : Europe, *Am : America
FS : Factory Setting
*Data Type is unsigned integer16
Code
Number
Function Name
Address
(Hex)
Address
(Dec)
R/W
attribute
Init.
Value
Min.
Value
Max.
Value
Scale
Unit
A70
PID Function Select
0x0346
839
R/W
0
0
2
A71
PID Setpoint
0x0347
840
R/W
0
0
10000
0.01
%
A72
PID Setpoint Source
0x0348
841
R/W
2
0
3
A73
PID Feedback Type
0x0349
842
R/W
0
0
1
A74
PID P Gain
0x034a
843
R/W
1000
1
10000
0.1
%
A75
PID I Gain Time
0x034b
844
R/W
10
0
36000
0.1
Sec
A76
PID D Gain Time
0x034c
845
R/W
0
0
1000
0.01
Sec
A77
PID Error Limit
0x034d
846
R/W
1000
0
1000
0.1
%
A78
PID Output High Limit
0x034e
847
R/W
1000
0
1000
0.1
%
A79
PID Output Low Limit
0x034f
848
R/W
0
-999
1000
0.1
%
A80
PID Output Invert
0x0350
849
R/W
0
0
1
A81
PID Scale Factor
0x0351
850
R/W
1000
1
10000
0.01
%
A82
Pre PID Frequency
Setpoint
0x0352
851
R/W
0
0
A04
0.01
Hz
A83
PID Sleep Frequency
Setpoint
0x0353
852
R/W
0
0
A04
0.01
Hz
A84
PID Sleep/Wake Delay
Time
0x0354
853
R/W
0
0
A04
0.01
Sec
A85
PID Wake Frequency
Setpoint
0x0355
854
R/W
0
0
A04
0.01
Hz
A61, A63
Data
Type
*signed integer16
Init value
of
A54,A55
A54 : 30000(A59=0), 390(A59=1), 290(A59=2)
A55 : 30000(A60=0), 390(A60=1), 290(A60=2)