N700E INSTRUCTION MANUAL
3-71
H05
Motor Rated Current
Range: 0.1 ~ 800.0 A in 0.1 A
Program a rated current off of the motor nameplate (Motor FLA)
Related Parameters:
H06
Motor Flux Current
Range: 0.1 ~ 400.0 A in 0.1 A
Program the no load (flux) current value. Not all motors will have this information on the
nameplate.
Related Parameters:
H07
Motor Rated Slip
Range: 0.01 ~ 10.0 % in 0.1 %
Program the slip percent of the motor rated nameplate rpm.
ie- [(1800 rpm – 1750 rpm) / 1800 rpm] x 100 = 2.78%
Related Parameters:
H08
Motor Resistance R1
Range: 0.1 ~ 3000.0 mOhms in 0.1 mOhms
Hyundai motor data
Related Parameters:
H09
Transient Inductance
Range: 0.001 ~ 30.000 mH in 0.001 mH
Hyundai motor data
Related Parameters:
H10
Motor Resistance R1 Auto Tuning Data
Range: : 0.1 ~ 3000.0 mOhms in 0.1 mOhms
Value determined during Auto Tuning process
Related Parameters:
H11
Transient Inductance Auto Tuning Data
Range: 0.001 ~ 30.000 mH in 0.001 mH
Value determined during Auto Tuning process
***Auto Tuning Application
Setting Procedures
H02:
H03:
H04:
H05:
H06
H07
Execution: Press “Run” Key
Successful Completion
; --oK
(if failed: Err on display)
H01: Select the latest to 1