N700E INSTRUCTION MANUAL
3-54
Set 9: Free Run Stop Command (FRS)
By activating FRS command, VFD stops the output and the motor coasts to stop.
Code
Set Value
Description
A02
1
Run Command by Terminal Input
C01
0
Set Terminal 1 to FW Operation
C03
9
Set Terminal 3 to FRS Operation
C07
0
Set Terminal 1 to Normal Open
When shorted(Closed); FW Run, When Open, FW Stop
C09
0
Set Terminal 3 to Normal Open
b03
[0.1~10]
Delay Time to VFD Restart
b16
0
Restart Frequency Set to 0Hz on FRS Cancellation (1: Resume M-Fre)
Motor
RPM
FW(Run)
t
b03
FRS
Free Run
i ) When b16 = 0
Motor
RPM
FW(Run)
t
FRS
i ) When b16 = 1
Free Run
CM1
6
P24
FW
5
4
3
2
1
FRS
Set 10: External Trip 1 (EXT)
By asserting a trip signal, it forces the VFD to stop and generates E12. Even when EXT
becomes inactive by opened the switch, the VFD remains the trip state. Thus, activating
reset signal or recycle the power must be done to clear the error state.
Code
Set Value
Description
A02
1
Run Command by Terminal Input
C01
0
Set Terminal 1 to FW Operation
C03
10
Set Terminal 3 to FRS Operation
C07
0
Set Terminal 1 to Normal Open
When shorted(Closed); FW Run, When Open, FW Stop
C09
0
Set Terminal 3 to Normal Open
CM1
6
P24
FW
5
4
3
2
1
EXT
MOTOR
RPM
FW(Run)
RST
Relay Alarm
Free Run
Trip State
EXT