N700E INSTRUCTION MANUAL
3-49
b56 ~ 60 System Load Detection Function
The drive provides two independent torque detection functions that trigger an alarm or fault signal when
the load is too heavy or suddenly drops
b56
System Load Detection Selection
0: Disabled
1: Overload Detection
2: Underload Detection
3: Overload/Underload Detection
4: Overload Detection with Fault (E23)
5: Underload Detection with Fault (E24)
6: Overload/Underload Detection with Fault (E23, E24)
For settings, 1~6 allows a relay contact to alert an external device, related parameters
C13, C14, C15. In addition, setting 4~6 triggers trip signals display on the keypad
b57
System Overload Detection Level
Range: 20.0 ~ 200.0 % in 0.1 %
Sets the System Overload level. This feature is triggered when the motor current exceeds
this level. 100% level is based off of the value in H05.
10% hysteresis
10% hysteresis
b59
b59
b57
Motor Current
System Overload Detection
b58
System Underload Detection Level
Range: 20.0 ~ 200.0 % in 0.1 %
Sets the System Underload level. This feature is triggered when the motor current
exceeds this level. 100% level is based off of the value in H05.
10% hysteresis
b59
b59
b58
Motor Current
System Underload Detection