N700E INSTRUCTION MANUAL
3-67
C18
FM Output Setting
Program what output performance to be monitored from following selections
0: Output Frequency Monitor
1: Output Current Monitor
2: Output Voltage Monitor
3: Output Power Monitor
4: Output Torque Monitor
5: Operation by Communication
Set 0: Output Frequency Monitor
Monitor the VFD output frequency value. The highest analog output value is the
maximum frequency value. The indicator accuracy after the adjustment is about +/- 5%.
Set 1: Output Current Monitor
Monitor the VFD output current value. The highest analog value is the 200% of rated
VFD current. The indicator accuracy after the adjustment is about +/- 10%.
Set 2: Output Voltage Monitor
Monitor the VFD output voltage value. The highest analog value is the 100% of rated
VFD voltage out. The indicator accuracy after the adjustment is about +/- 10%.
Set 3: Output Power Monitor
Monitor the VFD output power value. The highest analog value is the 200% of rated
VFD power out. The indicator accuracy after the adjustment is about +/- 10%.
Set 4: Output Torque Monitor
Monitor the VFD output torque value. The highest analog value is the 150% of rated
VFD output torque. The indicator accuracy after the adjustment is about +/- 10%
FM output
Torque
0V
-150%
5V
0%
10V
+150%
Set 5: Operation by Communication
It can control FM output value (0~10V) by Modbus command
Parameter
Address
Description
Analog Output (FM)
0x1004
0 ~ 10000
(0.1 scale, 0 ~ 10V, 0 ~ 100%)
Write Command has to set C18 = 5
Digital Output Bit Table
1
st
byte
Bit7
Bit6
Bit5
Bit4
Bit3
Bit2
Bit1
Bit0
Reserved
2
nd
byte
Bit7
Bit6
Bit5
Bit4
Bit3
Bit2
Bit1
Bit0
Reserved
AL0~2
RN2~3
RN0~1
C19
FM Gain