N700E INSTRUCTION MANUAL
3-12
3.1.6 Expanded Function Mode of H Group
Code
Name
Edit
Range
Unit Res Default
Motor Parameters
H01 Auto Tuning
X
0: OFF
1: ON
-
-
0
H02 Motor Data Select
X 0: Standard Data
1: Auto Tune Data
-
-
0
H03 Motor Capacity
X
3L(3 HP)
5L(5 HP)
7.5L(7.5 HP)
10L(10 HP)
15L(15 HP)
20L(20 HP)
25L(25 HP)
30L(30 HP)
40L(40 HP)
50L(50 HP)
60L(60 HP)
75L(75 HP)
100L(100 HP)
125L(125 HP)
3H(3 HP)
5H(5 HP)
7.5H(7.5 HP)
10H(10 HP)
15H(15 HP)
20H (20 HP)
25H (25 HP)
30H (30 HP)
40H (40 HP)
50H (50 HP)
60H (60 HP)
75H (75 HP)
100H (100 HP)
125H (125 HP)
150H (150 HP)
200H (200 HP)
250H (250 HP)
275H (275 HP)*
300H (300 HP)
350H (350 HP)*
400H (400 HP)
425H (425 HP)*
450H (450 HP)
500H (500 HP)
-
-
-
H04 Motor Poles Setting
X
2
4
6
8
4
H05 Motor Rated Current
X 0.1 to 800.0
A
0.1
-
H06 Motor Flux Current
X 0.1 to 400.0
A
0.1
-
H07 Motor Rated Slip
X 0.01 to 10.0
%
0.1
-
H08 Motor Resistance R1
X 0.1 to 3000.0
mΩ 0.1
-
H09 Transient Inductance
X 0.001 to 30.000
mH 0.001
-
H10
Motor Resistance R1 Auto
Tuning Data
X 0.1 to 3000.0
mΩ 0.1
-
H11
Transient Inductance
Auto Tuning Data
X 0.001 to 30.000
mH 0.001
-
* When b26 is set to 1, this motor series is displayed.(275H,350H,425H)