System Overload/Underload Detection Time
Range: 0.0 ~ 60.0 Sec in 0.1 Sec
Sets the System Overload/Underload Detection time.
b60
System Overload/Underload Detection safe zone
Range: 0.00 ~ Max frequency (A04) in 0.01 Hz
Sets the level at which this feature is disabled.
System Overload/Underload detection doesn’t work below b60 value
b61 ~ 64 Dwell Function
The Dwell Function temporarily holds the output frequency at a predetermined value for a
predetermined time before accelerating or decelerating to the current frequency reference. The Dwell
function helps preventing speed loss when starting and stopping a heavy load
B61 (Dwell time at start)
B62 (Dwell reference at start)
b63 (Dwell reference at stop)
B64 (Dwell time at stop)
F(Hz)
t
Run command
b61
Dwell Reference at Start
Range: 0.00 ~ Max frequency (A04) in 0.01 Hz
Program Dwell frequency at start
b62
Dwell Time at Start
Range: 0.0 ~ 10.0 Sec in 0.1 Sec
Program Dwell time at start
b63
Dwell Reference at Stop
Range: 0.00 ~ Max frequency (A04) in 0.01 Hz
Program Dwell frequency at stop
b64
Dwell Time at Stop
Range: 0.0 ~ 10.0 Sec in 0.1 Sec
Program Dwell time at stop