N700E INSTRUCTION MANUAL
3-56
Set 13: Analog Input Current / Voltage Select (AT)
If Shorted: Select Current Source
If Opened: Select Voltage Source
Code
Set Value
Description
A02
1
Run Command by Terminal Input
A01
1
Frequency Command by Terminal Input
C01
0
Set Terminal 1 to FW Operation
C05
13
Set Terminal 5 to AT Operation
C07
0
Set Terminal 1 to Normal Open
When shorted(Closed), Select Current Source; When Open, Voltage Source
C11
0
Set Terminal 5 to Normal Open
Caution
* If A01 is programmed to 1, but AT is not assigned on the terminal, VFD uses internal
algebraic sum of the voltage and the current inputs for the frequency value
CM1
6
P24
SFT
FW
5
4
3
2
1
CM1
6
P24
AT
FW
5
4
3
2
1
H
O
OI
L
VR
DC 12V
DC 0~10V
H
O
OI
L
DC 4~20mA
Input Voltage
Source Setup
Input Current
Source Setup
Set 14: Reset (RS)
Code
Set Value
Description
A02
1
Run Command by Terminal Input
C01
0
Set Terminal 1 to FW Operation
C04
14
Set Terminal 4 to ST Operation
C07
0
Set Terminal 1 to Normal Open
When shorted(Closed): FW Run, When Open: FW Stop
C10
0
Set Terminal 4 to Normal Open
Danger
*When Reset is asserted to clear the fault, if the RUN command is executed by FW/RV
terminal set, the motor will immediately run to the speed. Be sure to set the RS after RUN
command is disconnected in order to prevent
Caution
*If longer than 4 second is continued to be ON, E60, communication error will be displayed.
Reset by disconnect RS terminal to OFF or press STOP/RESET Key and resume VFD
operation to normal.