N700E INSTRUCTION MANUAL
3-66
Set 8: System Underload Detection (SUD)
The inverter System Underload is active by b58 level
Code
Set Value
Description
C13
8
Set Intelligent Relay Out 1 Terminal to SUD
C16
0
Set C13 to Normally Open to Form A configuration
If set to 1, Form B configuration (Normally Closed)
b56
2 or 5 or 6
System Underload Detection or Detection with Fault (E24)
b58
[20~200] % System Underload Detection Level
10% hysteresis
b59
b59
b58
Motor Current
System Underload Detection
@ OD signal LOW
AL0 AL1 AL2
AL0 AL1 AL2
@ OD signal HIGH
Set 9: System Overload/Underload Detection (SOD/SUD)
The inverter System Overload/Underload is active by the each(b57, b58) level
Code
Set Value
Description
C13
9
Set Intelligent Relay Out 1 Terminal to SOD/SUD
C16
0
Set C13 to Normally Open to Form A configuration
If set to 1, Form B configuration (Normally Closed)
b56
6
System Underload/Overload Detection with Fault (E23, E24)
b57
[20~200] % System Underload Detection Level
b58
[20~200] % System Underload Detection Level