N700E INSTRUCTION MANUAL
3-17
3.3 F Group Parameters
F group holds very basic frequency related parameter values to operate the N700E VFD.
F01
Output Frequency Setpoint
Range: 0.00 ~ 400.00 Hz in 0.01 Hz
Range: 0.00 ~ 300.00 Hz in 0.01 Hz for Sensor-less Vector Control (A31=2)
This parameter displays the frequency setpoint for the VFD.
VFD Frequency can be controlled by various sources set in A01.
If A01=0: Use the Volume Key on the panel
If A01=1: Use the Terminal (O-L, OI-L)
If A01=2: Use Up/Down Keys
If A01=3: Use Control Terminal Input (RJ45)
(Except 300LF~750LF)
If A01=4: Use Control Terminal Input,(RXP-RXN)
if A01=5: Fieldbus (option)
Related Parameters: A01
F02
Acceleration Time 1
Range: 0.1 ~ 999.9 Sec in 0.1 Sec
1000 ~ 3000 Sec in 1 Sec
Acceleration time from 0Hz to Maximum Frequency (A04)
Related Parameters: A54, A56, A57,A59
F03
Deceleration Time 1
Range: 0.1 ~ 999.9 Sec in 0.1 Sec
1000 ~ 3000 Sec in 1 Sec
Deceleration time from Maximum Frequency (A04) to 0Hz
Related Parameters: A55, A56, A58, A60
F04
Rotation Direction
0: Forward Run
1: Reverse Run
Sets the direction of VFD to forward or reverse at keypad operation only
Related Parameters: A02