N700E INSTRUCTION MANUAL
3-57
RS
Relay
Alarm
30mS
12 mS Minimum
CM1
6
P24
RS
FW
5
4
3
2
1
Danger:
*When Reset is asserted to clear the fault, if the RUN command is executed by FW/RV terminal set,
the motor will immediately run to the speed. Be sure to set the RS after RUN command is disconnected in
order to prevent any injury
Caution:
*If longer than 4 second is continued to be ON, E60, communication error will be displayed. Reset
by disconnect RS terminal to OFF or press STOP/RESET Key and resume VFD operation to normal.
Set 15: Start (STA)
3 Wire Run/Stop Application
Set 16: Keep (STP)
Set 17: Forward / Reverse (F/R)
Code
Set Value
Description
A02
1
Run Command by Terminal Input
C01
15
Set Terminal 1 to STA Operation
C02
16
Set Terminal 2 to STP Operation
C03
17
Set Terminal 3 to F/R Operation
C07
0
FW Operation: Terminal 1 to Normal Open
When shorted(Closed): FW Run, When Open: FW Stop
C08
0
FW Operation: Terminal 2 to Normal Open
C09
0
FW Operation: Terminal 3 to Normal Open
Set 18: Remote Control Up (UP)
Set 19: Remote Control Down (DOWN)
Code
Set Value
Description
A02
1
Run Command by Terminal Input
A01
Frequency Setting
C01
18
Set Terminal 1 to UP Operation
C02
19
Set Terminal 2 to Down Operation
C04
1
Set Terminal 3 to F/R Operation
C07
0
FW Operation: Terminal 1 to Normal Open
When shorted(Closed): FW Run, When Open: FW Stop
C08
0
FW Operation: Terminal 2 to Normal Open
CM1
1
2
3
4
5
6
P24
SW3
SW2
SW1
F/R
STP
STA
Stop Switch
(N.C)
Run Switch
(N.O)