N700E INSTRUCTION MANUAL
1-5
1.3.3 N700E Performance Specification
Features
Performance Specification
Control Method
(Note3)
V/f control, Sensorless Vector control
Output Frequency
Range
(Note4)
0.01
∼
400Hz (Sensorless Vector Control : 0.5
∼
300Hz)
Frequency Accuracy
Digital command ±0.01% of Max Frequency / Analog Frequency ±0.1% (25±10
℃
)
Frequency Resolution
Digital Setting : 0.01Hz (Under 100Hz), 0.1Hz (Over 100Hz)
Analog setting: Max. frequency / 1,000 (DC 0
∼
10V, 4
∼
20mA)
Voltage/frequency
Characteristic
Constant Torque, Variable Torque
Overload Current Rate
Heavy Duty(150%, 60sec), Normal Duty(120%, 60sec)
Acceleration/Deceleration
0.1
∼
3000 sec (Linear, S curve, U curve)
DC Injection Braking
Separately configurable start and stop up to 10 sec, 100 % motor rated current
Inp
ut
S
ign
al
Frequency
Set by Keypad (Potentiometer or Arrow Keys)
Input voltage: DC 0
∼
10V (Input impedance 10KΩ)
Input current: DC 4
∼
20mA (Input impedance 200Ω)
Run/Stop
Run / Stop key
Input Terminal: Forward Run/Reverse Run
Input Terminal: Start, Stop, FW/RV Selection
Intelligent Input
Terminal
FW(Forward Run), RV(Reverse Run),
CF1~4(Multi-speed Inputs 1~4),
RS(Reset),
AT(Analog input current/voltage selection signal),
USP(Unattended Start Protection)
EXT1~6(External trip 1~6),
FRS(Free-Run Stop),
JG(Jogging),
SFT(software lock),
2CH(2nd Acceleration / Deceleration),
STA, STP, F/R(3-wire)
UP, DOWN(Up/down), UP/DOWN initial value clear
O/R (Local Keypad Operation), T/R(Local Terminal Input Operation),
PIDIR(PID Integral Reset),
PIDD(PID Disabled)
F/O (Frequency Override), R/O (Reset Override)
Feature
Performance Specification
O
utp
ut
Si
gn
al
Intelligent Output
Terminal
(RN0-RN1,RN2-RN3,
AL0-AL1-AL2)
RUN(Run Status Signal),
FA1 (Frequency Arrival Signal 1),
FA2 (Frequency Arrival Signal 2),
OL(Overload Alarm),
OD(PID Error Deviation Signal),
FLT(Fault Signal)
COM(Operation by Communication)
SOL(System Overload)/SUL(System Underload)
FM Output
Analog Output Meter (DC 0~10V full scale. Max ∙ 1mA)
Output Frequency, Output Current, Output Voltage, Output Power, Output Torque,
Operation by Communication
AMI Output
Analog Output Meter (4~20mA full scale. Max ∙ 250Ω)
Output Frequency, Output Current, Output Voltage, Output Power, Output Torque,
Operation by Communication