N700E INSTRUCTION MANUAL
3-80
Note4: Read Only Command
Parameter
Address
Description
VFD Status
0x0001
0: Stop
1: Acceleration
2: Steady
3: Deceleration
4: Trip
Q-axis Current
0x000A
-2000 ~ 2000
(0.1 scale, -200.0 ~ 200.0 %)
Digital Input (1~6)
0x1000
Refer to below bit table
Analog Input (O)
0x1002
0 ~ 10000
(0.1 scale, 0 ~ 10V, 0 ~ 100%)
Analog Input (OI)
0x1003
0 ~ 10000
(0.1 scale, 4 ~ 20mA, 0 ~ 100%)
Digital Input Bit Table
1
st
byte
Bit7
Bit6
Bit5
Bit4
Bit3
Bit2
Bit1
Bit0
Reserved
2
nd
byte
Bit7
Bit6
Bit5
Bit4
Bit3
Bit2
Bit1
Bit0
Reserved
6
5
4
3
2
1
Note5: Read/Write Command
Parameter
Address
Description
Digital Output
(Relay Output)
0x1001
Refer to below bit table 0: Stop
Write Command has to set C13~C16 = 6
Analog Output (FM)
0x1004
0 ~ 10000
(0.1 scale, 0 ~ 10V, 0 ~ 100%)
Write Command has to set C18 = 5
Analog Output (AMI) 0x1005
0 ~ 10000
(0.1 scale, 4 ~ 20mA, 0 ~ 100%
Write Command has to set C25 = 5
Digital Output Bit Table
1
st
byte
Bit7
Bit6
Bit5
Bit4
Bit3
Bit2
Bit1
Bit0
Reserved
2
nd
byte
Bit7
Bit6
Bit5
Bit4
Bit3
Bit2
Bit1
Bit0
Reserved
AL0~2
RN2~3
RN0~1