N700E INSTRUCTION MANUAL
3-4
Code
Name
Edit
Range
Unit Res Default
Automatic Voltage Regulation (AVR) Function
A52 Automatic Voltage Regulation
(AVR)
X
0: Constant ON
1: Constant OFF
2: OFF during Deceleration
-
-
2
A53 Motor Input Voltage
X
230V class inverter settings:
200/220/230/240
460V class inverter settings:
380/400/415/440/460/480
-
-
LF Model
230V
HF Model
460V
2nd Acceleration and Deceleration Functions
A54 Acceleration Time 2
O 0.1 to 3000
Sec 0.1
30.0
A55 Deceleration Time 2
O 0.1 to 3000
Sec 0.1
30.0
A56 Accel/Decel 2 Command Select
X 0: [2CH] Input Terminal
1: Parameters (A54, A55, A57, A58)
-
-
0
A57 Accel 2 Transition Frequency
X 0.00 to Max Frequency (A04)
Hz 0.01
0.00
A58 Decel 2 Transition Frequency
X 0.00 to Max Frequency (A04)
Hz 0.01
0.00
A59 Acceleration Curve Select
X
0: Linea
1: S-curve
2: U-curve
-
-
0
A60 Deceleration Curve Select
X
0: Linear
1: S-curve
2: U-curve
-
-
0
A61 Analog Input Voltage Offset
O
-10.0 to 10.0
%
0.1
0.0
A62 Analog Input Voltage Gain
O
0.0 to 200.0
%
0.1
100.0
A63 Analog Input Current Offset
O
-10.0 to 10.0
%
0.1
0.0
A64 Analog Input Current Gain
O
0.0 to 200.0
%
0.1
100.0
A65 FAN Operation Mode
X
0: Always ON
1: ON only when VFD is running
FAN is running for 30 sec after
VFD stop
-
-
0