N700E INSTRUCTION MANUAL
3-61
CM1
6
P24
FW
5
4
3
2
1
EXT
MOTOR
RPM
FW(Run)
RST
Relay Alarm
Free Run
Trip State
EXT5 4
EXT6
3
2
OUTPUT
C13
Output Relay 1 (AL0, AL1, AL2)
Program one of following output command
0: RUN VFD Run Signal
1: FA1
Frequency Arrival 1
2: FA2
Frequency Arrival 2
3: OL
Overload Warning Signal
4: OD
Output Deviation Excess for PID Control
5: AL
Fault Signal
6: COM Operation by Communication
7: SOD System Overload Detection
8: SUD System Underload Detection
9: SOD/SUD System Overload/Underload Detection
AL0 AL1 AL2
If C13 = 0: When VFD is not Running
If C13 = 1: When Frequency is not Arrival 1
If C13 = 2: When Frequency is not Arrival 2
If C13 = 3:
When Overload condition isn’t occurred
If C13 = 4: When PID Error does not Exceed the Set Level
If C13 = 5: No fault condition is occurred
If C13 = 6: When it is not operated by modbus
If C13 = 7: When System Overload is not detected
If C13 = 8: When System Underload is not detected
If C13 = 9: When System Overload and Underload are not detected
If C13 = 0: When VFD is Running
If C13 = 1: When Frequency is at Arrival 1
If C13 = 2: When Frequency is at Arrival 2
If C13 = 3: When Overload condition occurred
If C13 = 4: When PID Error does Exceed the Set Level
If C13 = 5: Fault condition is occurred
If C13 = 6: When it is operated by modbus
If C13 = 7: When System Overload is detected
If C13 = 8: When System Underload is detected
If C13 = 9: When System Overload and Underload are detected
AL0 AL1 AL2
C14
Output Relay 2 (RN0-RN1)
C15
Output Relay 3 (RN2-RN3)
Program one of following output command below. These intelligent relay out terminals
can be configured to Form A or B type by programming C16 and C17 to 0 or 1.
0: RUN VFD Run Signal
1: FA1
Frequency Arrival 1
2: FA2
Frequency Arrival 2
3: OL
Overload Warning Signal
4: OD
Output Deviation Excess for PID Control
5: AL
Fault Signal
6: COM Operation by Communication
7: SOD System Overload Detection
8: SUD System Underload Detection
9: SOD/SUD System Overload/Underload Detection
C16~C17 Output Relay 2, 3 (RN0-RN1, RN2-RN3) Mode
0: Normally Open (NO) – Form A Configuration