N700E INSTRUCTION MANUAL
3-87
N700E
*Eu : Europe, *Am : America
FS : Factory Setting
*Data Type is unsigned integer16
Code
Number
Function Name
Address
(Hex)
Address
(Dec)
R/W
attribute
Init.
Value
Min.
Value
Max.
Value
Scale
Unit
b01
Restart Select
0x0401
1026
R/W
0
0
3
b02
Line Loss Ride-Through
Time
0x0402
1027
R/W
10
3
10
0.1
Sec
b03
Line Loss Ride-
Through Run Delay
0x0403
1028
R/W
10
3
100
0.1
Sec
b04
Motor Thermal Overload
Level
0x0404
1029
R/W
1000
200
1200
0.1
%
b05
Motor Thermal Overload
Profile
0x0405
1030
R/W
0
0
1
b06
Overload/Overvoltage
Restriction Mode
0x0406
1031
R/W
3
0
3
b07
Overload Restriction Level
0x0407
1032
R/W
HD:1800
ND:1500
(≤200 HP)
HD:1500
ND:1200
(≥250 HP,
300LF
~750LF)
200
5.5kW(7.5 HP)
~350kW(500
HP)
HD:2000
ND:1650
0.1
%
b08
Overload Restriction
Deceleration Rate
0x0408
1033
R/W
10
1
100
0.1
Sec
b09
Software Lock Mode
0x0409
1034
R
0
0
9999
b10
Start Frequency
Setpoint
0x040a
1035
R/W
50
50
1000
0.1
Hz
b11
PWM Carrier Frequency
0x040b
1036
R/W
50
5
055LF~150LF
MAX:160
055HF~150HF
MAX:160
185LF~750LF
MAX:100
185HF~1320H
F MAX:100
1600HF above
MAX:40
0.1
kHz
b12
Initialization Mode
0x040c
1037
R/W
0
0
1
b13
Country Code
0x040d
1038
R/W
0
1:*Eu
2:*Am
0
2
b14
RPM Display Scale Factor
0x040e
1039
R/W
100
1
9999
0.01
b15
Stop Key Function
0x040f
1040
R/W
0
0
1
b16
Resume Frequency
on FRS Cancellation
0x0410
1041
R/W
0
0
1
b17
Modbus Node ID
0x0411
1042
R/W
1
1
32
b18
Ground Fault Detection
Setpoint
0x0412
1043
R/W
0
0
1000
0.1
%
b19
Speed Search:
Current level
0x0413
1044
R/W
100
90
180
%
b20
Speed Search:
Voltage Increase
0x0414
1045
R/W
100
10
300
0.01
%
b21
Speed Search:
Voltage Decrease
0x0415
1046
R/W
100
10
300
0.01
%
b22
Speed Search:
Speed Decrease
0x0416
1047
R/W
1000
10
2000
0.1
%
b23
Frequency Match
0x0417
1048
R/W
0
0
1
b24
Fault Relay Select
0x0418
1049
R/W
0
0
1