N700E INSTRUCTION MANUAL
3-38
b25
Stop Method
0: Ramp to Stop
1: Coast to Stop (Free Run to Stop)
Select a stop method when Stop command is given.
Related Parameters:
b26
HD/ND (Torque Type) Select
0: Heavy Duty (HD): Constant Torque Load Type
1: Normal Duty (ND): Variable Torque Load Type
Select a torque type for appropriate “Rated Power” and “Overload Tolerance” values. For
instance, for Fans, or centrifugal pump applications, select ND and Hoists, conveyors,
pump process, select HD. Factory setting of Carrier Frequency value for HD and ND in
the table.
Related Parameters: b11
b27
Input Phase Loss Detection Period
0: Disabled
Range: 0 ~ 100 Sec in 1 Sec
Enables & sets the time period to determine if an Input Phase Loss occurs. The VFD
monitors the ripple on the DC bus voltage and if it occurs for the programmed magnitude
and time period an Input Phase Loss fault will occur. The ripple on the DC bus will cause
heating to the DC Bus capacitors which will shorten their life.
Related Parameters:
b28
Communication Time Out Detection
0: Disabled
Range: 0 ~ 60 Sec in 1 Sec
Select a time out detection period when communication discontinues. If no
communication event occurs during this time period, a communication fault will occur.
Related Parameters:
b29
Communication Time Out Detection Mode
0: Always Running
1: Only during VFD is Running
Select a time out detection mode.
Related Parameters:
b30
Display at Power On
Range: 1 ~ 13 (for d01 ~ d13)
Select an initial display parameter at power on
Related Parameters: