Devi
ce
Item
Data
Priority
The 802.1p priority is used: The priority of
the site information about the electrical
power system is 1 and the priority of
GOOSE packets is 5.
Table 17-6
Data plan for configuring automatic transmission of site information in the electrical
power system over Ethernet-ONU side
Device
Configurati
on Item
Data
Remarks
ONU_A
Inband
management
IP address
192.168.50.2/24
-
Traffic
profile
l
Index 10 (used for transmitting the
power distribution site
information)
l
Index 11 (used for transmitting
GOOSE packets)
-
Service port
Ethernet port: 0/1/1
Port 0/1/1 is used
for services on
terminal unit A.
Uplink port
GPON port
l
0/0/0: active uplink port
l
0/0/1: standby uplink port
-
Uplink
VLAN
l
Smart VLAN 8 (used for inband
management VLAN)
l
Smart VLAN 200 (used for
transmitting power distribution site
information)
l
Smart VLAN 100 (used for
transmitting GOOSE packets)
The uplink VLAN
must be the same
as the CVLAN on
the OLT.
Priority
The 802.1p priority is used: The
priority of power distribution site
information is 1 and the priority of
GOOSE packets is 5.
-
SmartAX MA5600T/MA5603T/MA5608T Multi-service
Access Module
Commissioning and Configuration Guide