MAN0923_Issue 3_04/15
Touchpoint Pro
Operating Instructions
73
5. User Interface
• Internet explorer 6.0 to 8.0
• Chrome up to V38
• Safari
• Chrome up to V38 on Android devices
5.6 PC Configuration Software
The optional PC Configuration Software is optimised for the larger screen of a PC, instead of the local
touchscreen. The menu and navigation are as detailed in the section “Menu Structure” however multiple
screens are combined, reducing the overall commissioning time.
Note: the PC Configuration Software is compatible with Windows 7. Please refer to Chapter 6,
Commissioning for the necessary settings.
5.7 SD Card
The SD card is used to store the event history of the system. Touchpoint Pro logs all events and all changes
to input readings. A notification will be given when the SD card is 80% full. If the card is not replaced, a
further notification will be given when it is full, and when data is being overwritten.
Note: A list of the events that are logged is given in Appendix 7 - Events
Caution: The SD Card must remain inserted during normal system operation. When the card is full it
should be replaced immediately
5.8 Interfaces
The Control Module has several communication interfaces:
•
10/100 Mbps Ethernet port for connection to a local network, to enable the Web Server function and
optional PC Configuration Software
•
Connections for the optional dual RS485 Modbus RTU interface
•
A USB port for connection to a USB flash drive, which can be used to save reports, backup
and restore configuration, and update software, firmware and the sensor catalogue
Note: The USB Device port is not EMC safe, and is to be used for maintenance mode only. The USB Host
port can take a USB flash drive, which can be left in place provided that it does not foul the cables or
cabinet door.