MAN0923_Issue 3_04/15
Touchpoint Pro
Operating Instructions
86
6. Commissioning
6.10 Commission Power Supply Unit Status Channels
Note: The PSU Status Inputs do not need to be used to monitor the power supplies if this function is not
required. They can also be configured to be used as Global Acknowledge, Global Reset or Global Inhibit.
1. If not already logged in, login with a valid administrator level user name
2. From the System Status screen select the
Extras
icon then
System Configuration
3. Re-enter the password and press
Login
4. Select
System Setup
5. The screen will show the system setup tree listing of all installed I/O modules, PSU Status Inputs and
Control Centre Board(s)
6. Select a Power Supply Unit Status channel, press the
Menu
icon and select
Commission Channel
7. Select the required parameters usijng the table below
Parameter Name
Default Setting
Value Range
Comment
Power Supply Unit Tag
PSU 1 Alarm
PSU 2 Alarm
PSU 3 Alarm
PSU 4 Alarm
30 characters
Event Type
Alarm
Alarm, Fault, Warning
Channel Type
Normal PSU
Ack Global, Reset Global, Inhibit Global
Default State
NO for Standard /
NC for Safe
Normally Closed (NC),
Normally Open (NO)
Input Latch
Non-Latching
Non-Latching, Latching
6.11 Redundant Control Centre Board Configuration
To access the Control Centre Board configuration:
1. If not already logged in, login with a valid administrator level user name
2. From the System Status screen select the
Extras
icon then
System Configuration
3. Re-enter the password and press
Login
4. Select
CCB Management
then
CCB Configuration
Access Level: Administrator
Parameter Name
Default Setting
Value Range
Comment
CCB Redundancy
Mode
Single CCB
Single CCB / Dual CCB
Only needs to be changed if a redundant CCB has been
added or removed