MAN0923_Issue 3_04/15
Touchpoint Pro
Operating Instructions
66
4. Electrical Installation
4.8.9 System State Relays
The System State Relay connections are found at TB4 and TB5 on the Control Module. They are rated at
30 Vdc 3 A or 250 Vac 3 A.
Caution: If the System State Relays are being used to switch AC voltages, an overcurrent protection
device must be included
Caution: Isolate all incoming supplies before making connections to the System State Relays
Note: It may be necessary to remove the Control Module Cover to make connections to the Control Module.
Do not remove any factory fitted earth cabling
Terminal
System Failure Relay
System Fault Relay
TB4
TB5
1
SIS_Fail_COM
SIS_Fault_COM
2
SIS_Fail_NO
SIS_Fault_NO
3
Screen_TB4
Screen_TB5
4.8.10 Power Supply Unit Status Inputs
The Power Supply Units Status Input connections can be found at TB8 and TB9 on the Control Module.
The PSU Status Inputs are Digital Input channels available for PSU monitoring. Alternatively, they can be
configured to be used as Global Acknowledge, Global Reset or Global Inhibit.
Note: It may be necessary to remove the Control Module Cover to make connections to the Control Module.
Do not remove any factory fitted earth cabling.
Terminal
System Failure Relay
System Fault Relay
TB8
TB9
1
PSU1_Stat 1
PSU3_Stat 1
2
PSU1_Stat 2
PSU3_Stat 2
3
PSU2_Stat 1
PSU4_Stat 1
4
PSU2_Stat 2
PSU4_Stat 2
5
Screen_TB8
Screen_TB9