MAN0923_Issue 3_04/15
Touchpoint Pro
Operating Instructions
111
8. Maintenance
The optional PC Configuration Software cannot be used while a test mode is active.
All events generated while the system is in test mode will be logged in the event history. Therefore a record
of the testing can be generated once it is complete (see Normal Operation, Generate Reports).
8.1.2 Field Inputs Test
Note: Engineer access level is required.
During this test, all field device inputs will be displayed by the Touchpoint Pro system, but the Cause and
Effect matrix will not be evaluated. No outputs will be generated.
The purpose of this test is to check that the input field devices are connected to the correct input channel of
the Touchpoint Pro system. Typically, this can be done either by applying gas to the sensor in the field or by
forcing the mA output of the sensor to a given value. The gas concentration and alarm states raised for the
channel can be viewed on the touchscreen or the Web Server.
To use the Field Inputs Test mode:
1. If not already logged in, login with a valid engineer level user name
2. From the
System Status
screen select the
Extras
icon then
Diagnostics
3. Press the
Menu
icon
and select
Field Inputs Test
4. The system will ask you to confirm, press
Yes
to proceed
5. The system will display a confirmation message, click on
OK
and you will be automatically navigated
to the
Active Events
screen
6. Proceed with the test of the field devices. To see more detailed information at any time, select the
channel of interest and select
Input Details
from the popup menu
Note: If the test is done from the
Active Events
screen, the channel of interest will be shown as soon as
its state changes, e.g. a threshold alarm is generated. Alternatively, you may wish to work from the
Inputs
screen (return to
System Status
screen and select
Inputs
) by scrolling down to the channel of interest
7. When the test is complete, return to the
System Status
screen and select the
Extras
icon then
Diagnostics
8. Press the
Menu
icon
and select
Stop Field Inputs Test
9. The system will show a confirmation message that it has returned to normal operation
WARNING
Ensure that the system is returned to normal operation once testing is complete.