MAN0923_Issue 3_04/15
Touchpoint Pro
Operating Instructions
207
15. Appendix 2 - Configurable
Parameter Reference Guide
15.3 Digital Input Module
The Digital Input Module has the option to configure a custom channel, or copy from a configured channel.
Note: The Digital Input will be treated as an alarm unless one of the Remote Interaction Settings is enabled
Note: If a channel is configured by copying from another channel, it is possible to edit individual settings
afterwards (see Section “Editing a Configured Channel”).
15.3.1 Commission Channel
Access Level: Administrator
Parameter Name
Default Setting
Value Range
Comment
Channel ID
Next available
1 to 64
Can only be assigned during first time configuration.
Otherwise de-commission the channel and re-assign
another channel number
Channel Location Tag “Channel <Channel ID>” Maximum 30
Alphanumeric Characters
30 character location tag name. This is the main
channel description used throughout the interface
Channel Custom ID
“Channel <Channel ID>” Maximum 20
Alphanumeric Characters
20 character custom ID. This is displayed on the
“Channel Details” screen and in the Configuration
Report
Note: Channel Location Tag and Channel Custom ID only require Engineer level access for editing
15.3.2 Digital Input Settings
Note: These parameters can only be set on first configuration. To edit later, it is necessary to decommission
and re-commission the channel.
Access Level: Engineer
Parameter Name Default Setting
Value Range
Comment
Input Type
Supervised OC/SC
Unsupervised /
Supervised OC /
Supervised OC/SC
A digital input (usually a switch) can be connected
unsupervised, supervised for open circuit (OC) or
supervised for both open circuit and short circuit (SC).
See Electrical Installation, Connections, Digital Input
Module for details
Default State
Normally Open (NO)
for Standard modules /
Normally Closed (NC) for
Safe modules
Normally Closed (NC) /
Normally Open (NO)
This parameter is not configurable for a SIL input channel