6. Commissioning
14. The system will return the new value, press
Accept
to confirm
15. Press
Exit
and close the menu window
16. Repeat steps 7 – 15 for each configured channel
17. Proceed to section 6.8
Figure 6.4 System Setup Data
6.8 Commission Input / Output Modules
Note: Administrator level access is required
1. If not already logged in, login with a valid administrator level user name
2. From the System Status screen select the
Extras
icon then
System Configuration
3. Re-enter the password and press
Login
4. Select
System Setup
5. If this is a first time configuration, the system will indicate that the Ring network must be initialised.
Press the
Ring Network
icon
to initialise the network manually
6. The screen will display the System Setup tree list of all Input / Output modules , PSU Status Inputs and
Control Centre Board(s) installed on the system. The modules are displayed in the order left to right on
the communication / power rail (looking at the rail), and in the direction of Ring A round the complete
system (if remote units are being used)
7. Select the required module, press the
Menu
icon
and select
Commission Module
8. Select a module ID number between 1 and 48 (the default is the next available number) and press
Send
to send it to the system
9. The system will then return the value, which will be displayed on the screen. Confirm that it is correct
and press
Accept
for the setting to take effect
10. Repeat for all un-commissioned modules on the system