8. Maintenance
8.4 How to replace a faulty I/O module
A faulty I/O module can be replaced with another of the same type, without needing to re-program the
configuration. Touchpoint Pro will automatically copy over the configuration to the new module.
WARNING
If the relays are switching mains voltages, hazardous live terminals may be present within the
Relay Output Module even if the Touchpoint Pro system is isolated.
Caution: When installing or replacing an I/O module, avoid static discharge
Note: Administrator level access is required
Note: The new module must be the same type as the old module.
1. Disconnect the field equipment from the faulty module, by unplugging the field terminals
2. Remove the faulty module from the Communication / Power Rail
•
Release the clip at the bottom of the module
•
Ease the module outwards and unhook it from the top of the DIN rail