6. Commissioning
Figure 6.3 PC Configuration Interface
6.7 Verify Default Configuration and Program Tags
Note: Read this section ONLY if your system has been programmed by Honeywell Analytics with the default
configuration during manufacture. Otherwise proceed to section 6.8
If the system has been delivered with a default configuration, then all Analogue Input channels (mA and mV)
have been configured. This section explains how to verify that the channel configuration is correct, and how
to program any tags that are required.
Note: It is necessary to configure any Digital Input channels and all Output channels
Note: Engineer level access is required
1. If not already logged in, login with a valid engineer level user name
2. From the System Status screen select the
Extras
icon then
System Configuration
3. Re-enter the password and press
Login
4. Select
System Setup
5. The screen will show a list of all installed I/O modules and Control Centre Board(s)
6. Press the + beside each module to expand and show the four channels of that module
7. Select the required channel, press the
Menu
icon
and select
View Configuration
8. Use the
Next
and
Previous
buttons to step through the configuration settings and verify that they
are as expected. If any settings are incorrect, please refer to the section “Editing a configured channel”
9. Press
Exit
10. Select the channel again, press the
Menu
icon and select
Edit Configuration
11. From the menu window select
Channel Name Settings
12. The screen will show the current location tag and custom ID
13. Enter the required values in the field
New Value
and press
Send