MAN0923_Issue 3_04/15
Touchpoint Pro
Operating Instructions
102
7. Normal Operation
A latched alarm can be reset in three ways:
1. Press the
Reset
button on the front panel of the Touchpoint Pro. This will reset ALL latched alarms,
faults and warnings, provided that the event has cleared. It will also reset any latched relay outputs
2. From the Inputs screen, select the channel and select
Reset
from the popup menu. This will reset all
latched events for the channel, provided that the input signal has returned to Normal status
3. From the Active Events screen, select the alarm and select
Reset
from the popup menu. This will reset
only the selected alarm
Note: The Reset button on the front panel of the Touchpoint Pro must be pressed for > 0.5 s to take effect.
7.5 Faults and Warnings
7.5.1 View Faults and Warnings
Detailed information about active Faults and Warnings can be viewed in two ways:
1. From the
System Status
screen, select either the Fault yellow triangle icon, or the Warning grey triangle
icon. The screen will show a filtered list of only the active Faults or Warnings.
2. Select the
Active Events
icon to show all active events, then the
Filter
icon and select
Fault
or
Warning
from the popup menu
Figure 7.11 Active Events Screen with filter options
7.5.2 Acknowledge an active Fault or Warning
Note: The system can be configured so that the
Accept
button is password protected and requires a user
to login (minimum Operator access level) via the touchscreen. See Commissioning, Control Centre Board
Configuration.
Note: Accept and Acknowledge have the same meaning in this context.