4. Electrical Installation
WARNING
Installation must be in accordance with the recognized standards of the appropriate authority
in the country concerned. Refer to local, national and company regulations.
4.1 Power Consumption
The power consumption of your system was calculated when it was ordered. Please refer to the Certificate
of Conformity supplied, or the rating plate for the power consumption.
4.2 Power Supply
WARNING
All power supplies must be hard wired and must include a circuit breaker (RCD / RCCB), and
(close by and unobstructed) a means of manually isolating and locking out the power supply
without breaking the true earth (ground) connection.
Removable plug and socket connection is not permitted under any circumstance.
4.2.1 AC Power Input
AC Power input (if used) must be single phase, 100 -- 240 Vac, 50/60 Hz.
The mains supply requires an overcurrent protection rated in accordance with the rating plate on the
specific system. The supply must be a fixed installation, i.e. not plug and socket. The supply must be
able to be isolated by means of a switch or circuit breaker, which must be suitably located, easily reached
and clearly marked as the Touchpoint Pro disconnect device. The wiring used between the isolator and
Touchpoint Pro must be appropriately rated and approved.