6. Commissioning
6.12 Buzzer Activation and Button Password Protection
The Touchpoint Pro buzzer can be configured to determine under which conditions it activates. There is also
a facility to password protect the Accept and Reset buttons on the Touchpoint Pro front panel.
1. If not already logged in, login with a valid administrator level user name
2. From the System Status screen select the Extras icon then System Configuration
3. Re-enter the password and press Login
4. Select CCB Management then CCB Configuration
Access Level: Administrator
Parameter Name
Default Setting
Value Range
Comment
Buzzer Activation
Threshold Alarms Only
Buzzer Off, Threshold Alarms Only, All
Alarms Only, All Events (All Alarms,
Faults, Inhibits and Warnings)
Determines the activation condition
for the buzzer
Password Protection for
Accept Button
Disabled
Enabled / Disabled
If enabled, Operator level access
is required to acknowledge active
events using the Accept button on the
front panel
Password Protection for
Reset Button
Enabled
Enabled / Disabled
If enabled, Operator level access is
required to reset active events using
the Reset button on the front panel
6.13 Touch Panel Configuration
To access the panel configuration:
1. If not already logged in, login with a valid engineer level user name
2. From the System Status screen select the
Extras
icon then
Global Settings
3. Select
Panel Configuration
Access Level: Engineer
Parameter Name
Default Setting
Value Range
Comment
Backlight Duration
15 minutes
10 seconds to 60 minutes
/ Always On
This is the time that the backlight will remain on after the
touchscreen is idle.
If a new event occurs, the backlight will come on and will
remain on as long as the event remains unacknowledged
Purpose of the
System Label
“Gas Monitoring
System”
30 characters
This text is displayed on the System Status screen