MAN0923_Issue 3_04/15
Touchpoint Pro
Operating Instructions
237
20. Appendix 7 - Logged events and
where they are displayed
Event
Comment
Displayed
Specific
Channel Type
(if applicable)
Input
Details
screen
Output
Details
screen
Active
Events
screen
Inputs /
Outputs
screen
Ring {0} Fault Cleared at
0 will be replaced by A or B
Ring Communication Error
If Module is in Fault all channels
of the Module will show Ring
Communication Error
✔
✔
All
Ring Communication Error
Cleared
All
Ring Oscillation Fault
TBC
Ring Oscillation Fault
Acknowledged
Ring Oscillation Fault Cleared
ROM Channel Modified
ROM
ROM User Inhibit
Channel has been inhibited by the
user
ROM User Inhibit Cleared
SD Card Full - Overwriting old
data
✔
SD Card inserted
SD Card memory 80% full
✔
SD Card missing
✔
SD card system ID mismatch
The inserted SD card contains data
from a different Touchpoint Pro
system
Sensor Catalogue
Logged when sensor catalogue is
updated
Sensor Lifetime Exceeded
Sensitivity of the mV sensor has
dropped below 50% of the original
value
✔
mV
Sensor Lifetime Exceeded
Cleared
mV
Session kill by UI
A user on the touchscreen has
ended another user’s login session
Session kill by PC
A user on the PC Configuration
Software has ended another user’s
login session
Short Circuit
TBC
✔
mA, mV
Short Circuit Cleared
mA, mV
Signal Over Range
Sensor mA or mV signal reading is
greater than the configured ‘Signal
Over Range Limit’
✔
mA, mV