SmartPAC 2 with WPC Integration
1126800
Installing SmartPAC 2 and WPC
Chapter 2
page 137
9. Notice whether “F48” appears on the display.
NOTICE
If the E-stop and top stops are not connected according to Figure 2 (end of this manual), the
status code may be different. Contact Wintriss Tech Support for assistance.
•
If F48 appears, go to the next step
•
If F48 does not appear, at the WPC control board, locate the “System Air Pressure”
LED on the WPC control board. It should
not
be illuminated. Check the wiring and
correct any problems. Push both RUN/INCH buttons at the same time. If F48 still
does not appear, contact Wintriss Tech Support.
10. Apply system air pressure to the press.
11. At the WPC control board, check whether the “System Air Pressure” LED is turned on.
Clear the error code on the display by pushing the RESET key.
12. Turn off the counterbalance air pressure and bleed down the counterbalance air pressure.
13. At the Operator Station, push both RUN/INCH buttons at the same time. The ram should
not move, and the error code should appear that is associated with the input the
counterbalance pressure switch is connected to. (See counterbalance pressure, error code
46, page 398.)
•
If the ram does not move and the appropriate error code appears, this is correct.
Restore the counterbalance air, push the RESET key and go on to the next step.
•
If the ram moves and/or if the appropriate code does not appear, check the wiring and
correct any problems. Push both RUN/INCH buttons at the same time. If the press
still runs and/or the appropriate code still does not appear, contact Wintriss Tech
Support.
NOTICE
If the E-stop and top stops are not connected according to Figure 2 (end of this manual), the
fault code may be different. Contact Wintriss Tech Support for assistance.
14. At the Operator Station, press the EMERGENCY STOP / RESET button. Go on to the
next test.
NOTICE
While the EMERGENCY STOP / RESET button is pressed, “F13” should appear on the
display.
Summary of Contents for SmartPAC 2
Page 192: ...1126800 SmartPAC 2 with WPC Integration Page 170 Chapter 2 Installing SmartPAC 2 and WPC ...
Page 294: ...1126800 SmartPAC 2 with WPC Integration Page 272 Chapter 4 SmartPAC 2 Initialization Mode ...
Page 342: ...1126800 SmartPAC 2 with WPC Integration page 320 Chapter 5 SmartPAC 2 Program Mode ...
Page 404: ...1126800 SmartPAC 2 with WPC Integration Page 382 Chapter 6 SmartPAC 2 Run Mode ...
Page 448: ...1126800 SmartPAC 2 with WPC Integration Page 426 Chapter 7 SmartPAC 2 Fault Messages ...
Page 476: ...1126800 SmartPAC 2 with WPC Integration page 454 Appendix C Updating SmartPAC 2 Firmware ...
Page 482: ...1126800 SmartPAC 2 with WPC Integration page 460 Appendix F Replacing SmartPAC 2 PC Board ...
Page 492: ...1126800 SmartPAC 2 with WPC Integration page 470 Glossary ...