Installation and commissioning
Generator installation for iMAPLA 25 and 30
5.6.3
Assembly (iMAPLA 25 and 30)
During assembly, observe the minimum clearances and specifications for
cooling in the following chapter.
Generator dimensions
Ö
Minimum clearances and cooling provisions, page 82
Secure the generator with at least four mounting
screws (minimum M12 or comparable, bolt grade
min. 8.8). The attachment must be permanent
and resistant to shock and vibrations. Use
suitable means to prevent the screws from
coming undone by themselves, e.g. via a tension
ring according to DIN 128.
y
Tightening torque for mounting screws: M =
87 Nm
y
Permissible load of the shaft: Fr
max
= 5,000 N
(measured in 60 mm axial clearance from the
point where the shaft exits the bearing plate)
Fa
max
= 500 N
Important
►
Do not attach any third party parts to
the mounting profiles on the generator
housing.
5.6.4
Minimum clearances and cooling provisions
y
The generator needs sufficient ventilation for cooling. The cooling air is
drawn through the cooling profiles by the fan wheel on the rear side of the
generator and across the housing, towards the front side.
y
Ensure adequate air feed and exhaust openings.
y
Comply with the following minimum clearances and note the regulations
for cooling.
4 Mounting screws
Fr
Fa
max
max